Single Output Industrial DIN Rail Power Supply (60W)

by Mean Well

This is an economical ultra slim 60W DIN rail power supply, designed to be installed on TS-35/7.5 or TS-35/15 mounting rails.

Features

  • ultra slim design with 52.5 mm (3SU) width
  • universal input 85-264 VAC (277 VAC operational)
  • no load power consumption <0.3 W
  • isolation class II
  • pass LPS (limited power source)
  • DC output voltage adjustable
  • protections: short circuit / overload / over voltage
  • cooling by free air convection (working temperature : -30 - +70°C)
  • DIN rail TS-35/7.5 or 15 mountable
  • over voltage category III
  • LED indicator power on
  • 3 year warranty
  • for professional use only
  • This device must be installed by a qualified person.

Specifications

Output
12 V - 4.5 A 24 V - 2.5 A
DC voltage 12 v 24 V
rated current 4.5 A 2.5 A
current range 0 - 4.5 A 0 - 2.5 A
rated power 54 W 60 W
ripple & noise (max.) 120 mVp-p 150 mVp-p
voltage adj. range 10.8 - 13.8 V 21.6 - 29 V
voltage tolerance ± 1.0 %
line regulation ± 1.0 %
load regulation ± 1.0 %
setup, rise time 500 ms, 50 ms / 230 VAC - 500 ms, 50 ms / 115 VAC at full load
hold up time (typ.) 30 ms / 230 VAC - 12 ms / 115 VAC at full load
  • input:
    • voltage range: 85-264 VAC (277 VAC operational) - 120-370 VDC (390 VDC operational)
    • frequency range: 47 - 63 Hz
    • efficiency (typ.): 90 % (24V) / 88% (12V)
    • ac current (typ.): 1.2 A / 115 VAC - 0.8 A / 230 VAC
    • inrush current (typ.): cold start 30 A / 115 VAC - 60 A / 230 VAC
  • protection:
    • overload:
      • 105 - 160 % rated output power
      • protection type: constant current limiting, recovers automatically after fault condition is removed
    • overvoltage:
      • 30 - 36 V (24V) / 14.2 - 16.2 V (12V)
      • protection type: shut down output voltage, re-power on to recover
  • environment:
    • working temperature: -30 to +70 °C
    • working humidity: 20 to 90 % RH non-condensing
    • storage: -40 to +85 °C, 10 to 95% RH
    • temperature coefficient: ± 0.03 %/°C (0 - 50°C )
    • vibration: 10 - 500 Hz, 2G 10 min / 1 cycle, 60 min each along X, Y, Z axes; mounting: compliance to IEC60068-2-6
    • operating altitude: 2000 m
    • over voltage category: III, according to EN61558, EN50178, EN60664-1, EN62477-1, altitude up to 2000 meters
  • safety & EMC:
    • safety standards: UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1 approved, design refer to TUV EN60950-1
    • withstand voltage: input to output: 4 kVAC
    • isolation resistance: input to output: 100 MOhm / 500 VDC / 25 °C / 70 % RH
    • EMC emission:
      • conducted: EN55032 (CISPR32) / Class B
      • radiated: EN55032 (CISPR32) / Class B
      • harmonic current: EN61000-3-2 / Class A
      • voltage flicker: EN61000-3-3
    • EMC immunity:
      • ESD: EN61000-4-2 / Level 3, 8KV air - Level 2, 4KV contact - criteria A
      • radiated susceptibility: EN61000-4-3 / Level 3 - criteria A
      • EFT/Burest: EN61000-4-4 / Level 3 - criteria A
      • surge: EN61000-4-5 / Level 4, 2KV/L-N - criteria A
      • conducted: EN61000-4-6 / Level 3 - criteria A
      • magnetic field: EN61000-4-8 / Level 4, criteria A
      • voltage dips and interruptions: EN61000-4-11 / >95% dip 0.5 periods, 30% dip 25 periods - >95% interruptions 250 periods
  • other:
    • MTBF: 927.6Kh, MIL-HDBK-217F (25 °C)
    • dimensions: 52.5 x 90 x 54.5 mm (w x h x d)

Downloads